Mantle Terminals DFG -_-E-AX with threaded stem - single conductor
Features
Metway explosion and firedamp-proof mantle terminals DFG-E-AX , millions of which have already proved their worth in practical applications, are suitable for installation in apparatus, machinery and installation equipment of all types.
They are mainly used in applications requiring a locked screw connection.
Metway mantle terminals provide maximum operational reliability and meet the requirements of the corresponding VDE regulations.
Technical Details
Clamping Range solid / flexible / AWG
DFG-1-E-AX: 0,14 – 6 mm²/0,14 – 4 mm²/26 – 12 AWG
DFG-2-E-AX: 0,14 – 6 mm²/0,14 – 6 mm²/26 – 10 AWG
DFG-3-E-AX: 0,2 – 10 mm² /0,2 – 10 mm²/24 – 8 AWG
DFG-5-E-AX: 0,2 – 25 mm²/0,2-16 mm²/24 – 6 AWG
Rated Cross Section
DFG-1-E-AX: 4 mm² [1]
DFG-2-E-AX: 6 mm² [2]
DFG-3-E-AX: 10 mm² [3]
DFG-5-E-AX: 25 mm² [4]
Rated Current max. load at 40°C/ 104°F ambient temperature
DFG-1: 30A
DFG-2: 39A
DFG-3: 53A
DFG-5: 95A
Torque
DFG-1-E-AX: 2 Nm
DFG-2-E-AX: 3,2 Nm
DFG-3-E-AX: 5 Nm
DFG-5-E-AX: 16 Nm
Options